Most drinking water plants were designed around chlorine. That made sense for decades, but today’s design problems look different: disinfection by-product limits, chlorine-resistant protozoa like Cryptosporidium, seasonal taste and odor, and source waters carrying iron, manganese, and organics all at once.

Ozone answers several of those problems in a single unit process. It is the strongest disinfectant and oxidant in routine drinking water use, it forms no chlorinated by-products on its own, and it leaves behind nothing but dissolved oxygen. The trade-off is that it rewards careful design: placement in the train, bromide, biological stability, and dose control all have to be addressed up front.

This guide is for consulting engineers evaluating ozone for a new plant or an upgrade. It covers what ozone does in a drinking water plant, how it compares to chlorine-based alternatives, the design decisions that matter most, and where a packaged Guardian Ozone system fits.

What ozone does in a drinking water plant

EPA’s guidance on alternative disinfectants groups ozone’s drinking water uses into four jobs. Most plants that install ozone use it for more than one.

  • Primary disinfection. Ozone achieves inactivation with less concentration and contact time than chlorine, chlorine dioxide, or monochloramine. EPA ranks it more effective than all three against viruses, Giardia, and Cryptosporidium, and one study found Cryptosporidium roughly ten times more resistant to ozone than Giardia, but still treatable.
  • Inorganic oxidation. It oxidizes iron, manganese, and sulfide so they can be filtered out.
  • Micropollutant oxidation. It destroys many taste and odor compounds, phenolic compounds, and some pesticides. Most early U.S. ozone plants were installed specifically for taste and odor.
  • Organics and DBP control. It removes color, makes natural organic matter more biodegradable, and lets free chlorine be applied later in the plant, at lower doses and after precursors have been removed.

One limit shapes every design: ozone cannot be the secondary disinfectant. Its residual decays too quickly to protect the distribution system, so it is always paired with chlorine, chloramine, or chlorine dioxide downstream.

The adoption curve reflects these benefits. EPA counted about 40 larger U.S. plants using ozone in 1991 and 264 by 1998, and most of those were small systems under 1 MGD.

Ozone vs. chlorine-based options

The question is rarely ozone instead of chlorine. It is whether ozone should take over primary disinfection and oxidation, so chlorine can do less, later, as the residual.

Consideration Free chlorine Chloramine Chlorine dioxide Ozone
Protozoa (Giardia, Crypto) Weak against Crypto Weak Moderate Strongest of the four
Viruses and bacteria Effective Slow Effective Very effective, short contact time
Halogenated DBPs (THMs, HAAs) Forms them Low Low; forms chlorite None from ozone alone
Bromide waters Brominated DBPs Lower risk — Bromate risk; needs control
Fe, Mn, sulfide, taste and odor Partial Poor Good Strong
Distribution residual Yes Yes, long-lasting Limited No; needs a secondary disinfectant
Chemical storage on site Yes Yes Yes No; generated on site

EPA also lists ozone’s costs plainly: higher capital cost, energy for on-site generation, a toxic and corrosive gas to contain, and the need for biologically active filtration to manage the biodegradable organics ozone creates. A good design accounts for each of these instead of discovering them at startup.

Design considerations

  1. Choose the feed point from water quality. EPA’s small-system guidance ties ozone placement to raw water turbidity and ozone demand. Moving ozone downstream of sedimentation lowers demand and by-product formation; placing it ahead of filtration lets the filters remove biodegradable organics.
Raw water Recommended ozone feed point
Turbidity < 10 NTU, demand < 1 mg/L Raw water or after sedimentation
Turbidity > 10 NTU, demand < 1 mg/L After sedimentation
Turbidity < 10 NTU, demand > 1 mg/L Raw water and/or after sedimentation
Turbidity > 10 NTU, demand > 1 mg/L After sedimentation, and after first-stage filtration if needed
  1. Size contact for CT, after demand is met. Iron, manganese, organics, and taste and odor compounds consume ozone before a measurable residual develops. Contactor volume is set from the applied dose and expected residual to meet the CT target, with plug-flow hydraulics and transfer efficiency above about 80%.
  2. Test for bromide early. Bromate becomes an important consideration above roughly 0.10 mg/L bromide, and systems using ozone must monitor bromate monthly. Control options include lowering pH, lowering the ozone residual, and ammonia addition, each with trade-offs.
  3. Plan for biological stability. Ozone breaks large organic molecules into smaller, biodegradable ones. Without biologically active filtration, that material can drive regrowth in distribution. With it, the plant gets lower BDOC, lower DBP precursors, and a lower chlorine demand.
  4. Coordinate the secondary disinfectant. Ozone reduces downstream chlorine demand, but certain by-products can form when chlorine follows ozone without biofiltration in between. Monochloramine or biofiltration ahead of chlorination limits those interactions.
  5. Design safety in. Off-gas must be destroyed to below the 0.1 ppm OSHA exposure limit before venting, and generator spaces need continuous ambient monitoring with alarms and shutdown interlocks.
  6. Decide on redundancy. EPA notes that backup generator units are usually installed. If ozone carries disinfection credit, plan for generator service without losing treatment.

Where Guardian Ozone fits

Guardian’s drinking water treatment application uses the ATS Series, a packaged aqueous ozone system.

  • The full ozone system in one skid. EPA describes four basic components: gas feed, generator, contactor, and off-gas destruct. The ATS packages generation, oxygen supply, mass transfer, contact, monitoring, and closed-loop control together, so the design team specifies one system instead of integrating four.
  • Dose follows demand. Closed-loop control matches ozone output to treatment demand, the approach EPA recommends to avoid energy-wasting overdosing.
  • Air-cooled generation. No cooling-water loop to design, pipe, or protect.
  • Built for small and mid-size systems. Most U.S. ozone plants serve small communities, and a packaged system keeps ozone practical at that scale.
  • Redundancy available. A dual-generator 2X configuration keeps treatment running during generator service .

Talk to us early in design

Send us your raw water data, including turbidity, TOC, alkalinity, pH, bromide, iron, manganese, and design flow, along with your disinfection targets. Guardian Ozone’s application engineers will help you choose the feed point, estimate ozone demand, and size a system your team can carry into design.